Top 20 Temperature Element Faults & Fixes: A Comprehensive Guide

Temperature elements are the unsung heroes of countless industrial processes, from ensuring the safety of food production to optimizing chemical reactions. When these critical components fail, the consequences can range from minor production inefficiencies to catastrophic equipment damage. This guide details the top 20 most common temperature element faults and provides clear, actionable fixes to get your operations back on track swiftly.

The following questions and answers address issues with the most prevalent temperature sensors—thermocouples, resistance temperature detectors (RTDs), and thermistors—as well as the broader temperature measurement system.

I. Sensor-Specific Faults & Fixes

1. Question: Why is my temperature reading erratic or jumping around?

Fix: Erratic readings often point to loose connections, intermittent short circuits, or electromagnetic interference (EMI).

  • Check all wiring connections from the sensor to the transmitter or controller. Ensure terminals are tight and free of corrosion.
  • Inspect the sensor sheath and wiring insulation for any signs of damage, which could cause a short.
  • Reroute sensor wiring away from power cables, motors, and other sources of EMI. If rerouting isn’t possible, use shielded twisted-pair wiring and ensure the shield is properly grounded at one end.

2. Question: My display shows an “Open” or “OL” error, indicating a very high temperature.

Fix: This almost always signifies a break in the sensing element or its wiring.

  • For thermocouples, the fine internal wires can break due to vibration or metal fatigue. A simple continuity test with a multimeter across the two leads will confirm an open circuit. Replace the thermocouple.
  • For RTDs, the delicate wire-wound or thin-film element can fracture. Measure the resistance between the leads. An infinite reading confirms a break. Replace the RTD.

3. Question: The temperature reading is fixed at a very low or negative value.

Fix: This typically indicates a short circuit within the sensor or its wiring.

  • Visually inspect the sensor and its wiring for any crushed or damaged sections where the leads might be touching.
  • Use a multimeter to measure the resistance between the sensor leads. A reading of near-zero ohms confirms a short. For thermocouples, this will result in a temperature reading corresponding to the ambient temperature at the point of the short. Replace the faulty sensor or wiring.

4. Question: The temperature reading has drifted and is no longer accurate.

Fix: Sensor drift is a gradual change in the output signal over time and is common with thermocouples, especially at high temperatures.

  • Recalibrate the sensor against a known temperature standard. This can be a certified reference probe or an ice bath (0°C).
  • If the drift is significant and cannot be corrected by calibration, the sensor has likely degraded due to prolonged exposure to high temperatures, chemical attack, or mechanical stress. The sensor will need to be replaced.

5. Question: Why are my thermocouple readings inaccurate after I replaced the wire?

Fix: Using the wrong type of extension wire is a frequent mistake.

  • Ensure the extension wire material matches the thermocouple type (e.g., Type K thermocouple requires Type K extension wire). Using a different type will create an unwanted thermocouple junction, leading to significant errors. The color coding on the insulation should be checked against ANSI or IEC standards.
  • Verify the polarity is correct. Reversing the positive and negative leads will also cause inaccurate readings.

6. Question: My RTD reading is slightly off, and calibration doesn’t seem to last.

Fix: This can be caused by self-heating or lead wire resistance issues in 2-wire RTDs.

  • Reduce the excitation current from the controller or transmitter if possible. Excessive current can cause the RTD element to heat up, leading to a higher-than-actual temperature reading.
  • For long wire runs with 2-wire RTDs, the resistance of the lead wires can add to the sensor’s resistance, causing a positive error. Either perform a lead wire resistance compensation in the controller or switch to a 3-wire or 4-wire RTD configuration, which automatically compensates for this.

7. Question: My thermistor readings are out of range.

Fix: Thermistors are highly sensitive and can be damaged by over-temperature conditions.

  • Verify the thermistor has not been exposed to temperatures beyond its specified operating range.
  • Check the resistance with a multimeter and compare it to the manufacturer’s resistance-temperature curve. A significant deviation indicates a damaged thermistor that needs replacement.

II. Installation and Environmental Faults

8. Question: The temperature reading is consistently too high or too low.

Fix: Improper sensor placement is a common culprit.

  • Ensure the sensor is fully inserted into the process to the required immersion length.
  • Position the sensor in a location that is representative of the true process temperature, away from stagnant areas, dead legs, or direct heat sources/sinks that are not part of the process being measured.
  • For surface measurements, ensure good thermal contact. Use thermal paste or a mounting pad to minimize air gaps.

9. Question: The sensor is failing prematurely.

Fix: The sensor may not be rated for the operating environment.

  • Verify that the sensor’s sheath material is compatible with the process chemicals to prevent corrosion.
  • Ensure the sensor is rated for the process temperature and pressure.
  • Protect the sensor from excessive vibration by using a thermowell or a more robust sensor design.

10. Question: The temperature reading is unstable after washing down the equipment.

Fix: Moisture ingress into the sensor head or wiring is a likely cause.

  • Ensure the sensor head has a proper gasket and is securely tightened. Use a conduit and fittings with an appropriate NEMA or IP rating for the environment.
  • Dry out the connections and check for any corrosion. Replace any damaged components.

11. Question: My thermowell seems to be affecting the reading.

Fix: An air gap between the sensor and the thermowell can slow response time and cause inaccuracies.

  • Ensure the sensor is bottomed out in the thermowell. Spring-loaded sensors are ideal for this.
  • Use a heat transfer fluid or paste inside the thermowell to improve thermal conductivity between the well and the sensor.

III. System and Controller Faults

12. Question: The temperature controller displays an error code.

Fix: Refer to the controller’s manual for the specific error code. Common causes include sensor burnout, a disconnected sensor, or an internal controller fault. The manual will provide targeted troubleshooting steps.

13. Question: The controller is not sending a correct output signal (e.g., to a heater or valve).

Fix: This could be a tuning issue or a hardware problem.

  • Check the PID tuning parameters. Poorly tuned controllers can cause the temperature to overshoot, undershoot, or oscillate. Perform an auto-tune cycle or manually adjust the PID values.
  • Verify the controller’s output relay or analog output is functioning correctly.

14. Question: I have reversed the polarity on my thermocouple. What happens?

Fix: Reversing the leads will cause the temperature reading to move in the opposite direction from the actual temperature change. For example, as the temperature rises, the reading will drop. Correct the wiring by ensuring the positive lead from the thermocouple is connected to the positive terminal on the instrument and the negative lead to the negative terminal.

15. Question: Can I ground a thermocouple in multiple locations?

Fix: No, this creates a ground loop, which can induce noise and errors in the reading. A thermocouple circuit should only be grounded at a single point, typically at the controller or transmitter.

16. Question: My new universal transmitter is not reading the sensor correctly.

Fix: The transmitter is likely configured for the wrong sensor type or range.

  • Access the transmitter’s configuration menu and ensure the selected sensor type (e.g., Type K TC, Pt100 RTD), temperature units (°C or °F), and measurement range are correct for your application.

17. Question: The temperature reading is correct at the sensor but wrong at the control room.

Fix: This suggests a problem with the signal transmission.

  • For analog signals (4-20mA), check for a current drop due to excessive loop resistance or a failing power supply.
  • For digital signals (e.g., HART, Fieldbus), check for communication errors, incorrect addressing, or network issues.

18. Question: Why is my RTD reading fluctuating when a nearby motor starts?

Fix: This is a classic sign of EMI.

  • Ensure shielded cable is used for the RTD signal and that the shield is grounded at the controller/transmitter end only.
  • Physically separate the sensor wiring from the motor’s power cables.

19. Question: The controller’s display is blank.

Fix: This indicates a loss of power to the controller.

  • Check the main power supply, fuses, and circuit breakers.
  • Verify the power connections to the controller are secure.

20. Question: My process temperature is oscillating even with a PID controller.

Fix: Besides poor PID tuning, this can be caused by an oversized heater or an undersized cooling system.

  • Retune the PID loop.
  • If tuning doesn’t solve it, evaluate the physical system. The heating or cooling element may be too powerful for the process, causing rapid temperature changes that the controller cannot manage effectively. Consider a smaller control element or using a time-proportioned output.

By systematically working through these common issues, you can efficiently diagnose and resolve the vast majority of temperature element faults, ensuring the continued accuracy and reliability of your temperature measurement systems.