An I/O (Input/Output) list for a Distributed Control System (DCS), Instrumented Protective System (IPS/ESD), or Fire and Gas System (FGS) in the oil and gas sector is typically a comprehensive spreadsheet or database. It serves as a master reference for all instrument signals connected to these control and safety systems.

The format is a detailed table with specific columns that define every attribute of each input and output point.


Typical IO List Format

The document is structured as a table where each row represents a single I/O point. The columns detail the specific attributes of that point. While the exact columns can vary slightly between projects and companies, the following are standard.

Column HeaderDescriptionExample
Tag NumberThe unique alphanumeric identifier for the instrument or I/O point. This is the primary key.10-PT-101A
Service DescriptionA brief, clear description of the instrument’s function or the process it measures/controls.Pump P-101A Discharge Pressure
P&ID No.The Piping and Instrument Diagram number where the instrument is shown.PID-100-001
SystemThe control system the I/O point is assigned to.DCS, IPS, FGS
I/O TypeThe type of signal. Common types include AI, AO, DI, DO.AI (Analog Input)
Signal TypeThe specific electrical signal characteristics.4-20mA, 24VDC, HART
Controller / Logic SolverThe specific controller, PLC, or logic solver that will process this I/O point.DCS Controller 01
I/O Card TypeThe specific model number of the I/O card where the signal will be terminated.AI-HART 8-Channel
Cabinet No.The identification number of the system cabinet housing the I/O card.DCS-CAB-01A
Slot No.The specific slot or rack location of the I/O card within the cabinet.03
Channel No.The channel number on the I/O card to which the signal is wired.05
Range (Low / High)The engineering unit range for analog signals.0 / 10
UnitsThe engineering units of measurement for the process variable.barg
Alarm (LL/L/H/HH)Setpoints for Low-Low, Low, High, and High-High process alarms.0.5 / 1.0 / 8.5 / 9.0
RemarksAny additional relevant information, notes, or special requirements.Requires Intrinsically Safe barrier

 

Key System Designations

 

  • DCS (Distributed Control System): Manages process control and monitoring. Handles standard analog and digital signals for regulating the plant.

  • IPS (Instrumented Protective System) / ESD (Emergency Shutdown): A safety-critical system (SIS – Safety Instrumented System) that takes automatic action to prevent hazardous events. Its I/O is separate and redundant from the DCS.

  • FGS (Fire and Gas System): Detects fires and combustible/toxic gas leaks and initiates alarms, suppression, and shutdown actions. It’s also a safety-critical system.

The I/O list is a foundational document used by multiple disciplines (Instrumentation, Process, Electrical, Automation) throughout the project lifecycle, from design and procurement to configuration and commissioning.

 

 

 