HART Temperature Transmitters: Top 10 Questions Answered

Answering the most critical questions surrounding the operation, calibration, and benefits of HART-enabled temperature transmitters in industrial processes.

HART (Highway Addressable Remote Transducer) protocol has become a cornerstone of modern industrial automation, enabling enhanced communication with smart field devices. When it comes to temperature measurement, HART temperature transmitters offer significant advantages over traditional analog-only devices. Here are the answers to the top 10 questions surrounding these intelligent instruments.

1. What is a HART Temperature Transmitter?

A HART temperature transmitter is a device that converts the signal from a temperature sensor (such as a thermocouple or RTD) into a standard 4-20mA analog signal, while simultaneously superimposing a digital communication signal on the same wires. This digital signal, based on the HART protocol, allows for two-way communication with the transmitter for configuration, diagnostics, and monitoring.

2. How Does HART Communication Work with a Temperature Transmitter?

HART communication utilizes the Bell 202 Frequency Shift Keying (FSK) standard to overlay a low-level digital signal on top of the 4-20mA analog current loop. The digital signal consists of two frequencies: 1200 Hz representing a “1” and 2200 Hz representing a “0”. This allows for simultaneous transmission of the primary process variable (temperature) via the analog signal and additional digital information without requiring separate wiring.

3. What are the Key Advantages of Using a HART Temperature Transmitter?

The primary benefits of employing a HART temperature transmitter include:

  • Remote Configuration: Users can remotely configure transmitter parameters such as sensor type, measurement range (URV/LRV), and damping from a control room or handheld communicator, reducing time spent in potentially hazardous areas.
  • Enhanced Diagnostics: HART-enabled transmitters continuously perform self-diagnostics and can report issues like sensor failure, open or short circuits, and internal hardware faults. This proactive maintenance approach minimizes downtime.
  • Improved Accuracy: The ability to digitally trim the transmitter’s output to precisely match the sensor’s characteristics results in a more accurate and reliable temperature measurement.
  • Asset Management: Digital communication allows for easy access to device information such as tag numbers, descriptions, and calibration history, simplifying asset management and maintenance records.
  • Multi-Variable Data: Some HART transmitters can transmit additional process variables, such as sensor resistance or internal temperature, along with the primary temperature reading.

4. How Do I Calibrate a HART Temperature Transmitter?

Calibrating a HART temperature transmitter involves a few key steps:

  1. Isolate the Process: Ensure the transmitter is isolated from the process to prevent any live temperature from affecting the calibration.
  2. Connect a Calibrator: A temperature calibrator is used to simulate the sensor input (e.g., millivolts for a thermocouple or ohms for an RTD).
  3. Connect a HART Communicator: A handheld HART communicator or a PC with a HART modem is connected to the 4-20mA loop.
  4. Perform a “Trim”: Using the communicator, a “sensor trim” is performed at a lower and upper range value. This adjusts the digital reading of the transmitter to match the precise input from the calibrator.
  5. Perform an “Output Trim”: An “output trim” adjusts the 4mA and 20mA analog outputs to correspond accurately to the lower and upper range values.

5. What is the Difference Between “Sensor Trim” and “Output Trim”?

  • Sensor Trim (or Digital Trim): This procedure adjusts the digital reading of the transmitter to match the input from the sensor simulator (calibrator). It ensures the core digital measurement is as accurate as possible. This is the most critical adjustment for accurate temperature representation.
  • Output Trim (or D/A Trim): This adjusts the digital-to-analog converter within the transmitter. It ensures that the 4mA and 20mA analog signals accurately represent the digitally measured temperature. This trim is important for systems that rely on the analog signal for control.

6. Can I Use a HART Transmitter with a Non-HART Control System?

Yes. A HART temperature transmitter will function as a standard 4-20mA analog transmitter when connected to a non-HART enabled control system. The primary variable (temperature) will be communicated via the analog signal. However, you will lose the benefits of digital communication, such as remote configuration and advanced diagnostics. A handheld HART communicator can still be used to configure and troubleshoot the device in the field.

7. What is a “Multidrop” HART Configuration?

A multidrop configuration allows multiple HART devices to be connected on a single pair of wires. In this setup, the analog 4-20mA signal is disabled (fixed at 4mA), and all communication occurs digitally. Each transmitter is assigned a unique polling address (from 1 to 63). The host system then polls each device sequentially to retrieve its process data. This configuration is useful for monitoring multiple points where high-speed updates are not critical.

8. What are Common Faults Detected by HART Temperature Transmitters?

HART transmitters can diagnose and report a variety of faults, including:

  • Sensor Failure: Detects if the connected thermocouple or RTD has failed (open or shorted).
  • Out-of-Range Condition: Indicates that the measured temperature is outside the configured upper or lower range values.
  • Hardware Faults: Internal electronic issues within the transmitter itself.
  • Loop Integrity Issues: Can detect if the current loop is open or if the loop current is not within the expected 4-20mA range.
  • Configuration Errors: Reports inconsistencies in the transmitter’s setup.

9. What is the Role of a Device Description (DD) File?

A Device Description (DD) is a file provided by the transmitter manufacturer that contains all the information about the device’s capabilities and how to communicate with it. HART host systems and communicators use the DD file to understand the specific commands, menus, and data structures of a particular transmitter. This “plug-and-play” capability allows for seamless integration of devices from different manufacturers.

10. How Do I Troubleshoot a HART Temperature Transmitter?

Troubleshooting a HART temperature transmitter typically involves a systematic approach:

  1. Check Physical Connections: Ensure the wiring for the sensor and the 4-20mA loop is secure and correct.
  2. Verify Loop Power: Confirm that the transmitter is receiving the correct supply voltage.
  3. Use a HART Communicator: Connect a communicator to check the device status. The communicator will display any diagnostic alerts or error messages from the transmitter.
  4. Check the Digital and Analog Readings: Compare the digital process variable reading on the communicator with the analog mA output to identify any discrepancies.
  5. Review Configuration: Verify that the transmitter is configured correctly for the specific sensor type and desired measurement range.
  6. Simulate Input: If possible, disconnect the sensor and use a calibrator to simulate a known input to test the transmitter’s functionality independently of the sensor.