Orifice Plate Flow Meters – 20 Common Interview Questions

Orifice Plate Flow Meters

20 Most Common Interview Questions & Answers

1. What is the basic working principle of an orifice plate flow meter?

An orifice plate flow meter operates on Bernoulli's principle. It consists of a thin plate with a precisely machined hole (orifice) inserted into a pipe. As the fluid passes through the smaller orifice, its velocity increases and its pressure decreases. The flow rate is calculated by measuring this pressure difference (differential pressure) across the plate.

2. What are the main components of an orifice meter assembly?

The main components are:

  • Orifice Plate: The plate with the hole that creates the restriction.
  • Orifice Flanges: Special flanges to hold the plate and provide pressure taps.
  • Pressure Taps: Holes in the pipe or flanges to measure upstream and downstream pressure.
  • Differential Pressure (DP) Transmitter: A device to measure the pressure drop and convert it into a flow signal.

3. Explain the term "Vena Contracta." Why is it important?

The Vena Contracta is the point of minimum cross-sectional area of the fluid stream, which occurs just downstream of the orifice plate. At this point, the fluid velocity is at its maximum and the pressure is at its minimum. It's the ideal location for the downstream pressure tap to measure the lowest pressure for the most accurate differential pressure reading.

4. What is the "Beta Ratio" (β) and what is its significance?

The Beta Ratio is the ratio of the orifice bore diameter (d) to the internal pipe diameter (D), so β = d/D. It's a critical design parameter. A typical range for β is between 0.2 and 0.75. A higher beta ratio means less pressure drop but lower accuracy, while a lower beta ratio provides higher accuracy but causes a greater permanent pressure loss in the system.

5. Describe the different types of orifice plates.

  • Concentric: The most common type, with the orifice in the center. Used for clean, single-phase fluids.
  • Eccentric: The orifice is offset to the bottom. Used for fluids containing solids to prevent buildup.
  • Segmental: Has a segment-shaped opening at the top or bottom. Used for slurries or fluids with high solids content.
  • Quadrant Edge: Has a rounded edge on the upstream side. Used for viscous fluids with low Reynolds numbers.

6. When would you use an eccentric or segmental orifice plate?

You would use an eccentric or segmental plate when dealing with two-phase or multiphase flows. For example, in a horizontal pipe carrying a liquid with entrained solids, an eccentric plate with the bore at the bottom allows the solids to pass through, preventing damming. For a liquid with entrained gas, the bore would be at the top to let the gas pass.

7. What are the main advantages of using an orifice plate flow meter?

  • Low cost and simple construction.
  • No moving parts, making them robust and reliable.
  • Well-understood technology with extensive standards (e.g., ISO 5167, AGA 3).
  • Can be used for a wide range of pipe sizes and fluid types (liquids, gases, steam).

8. What are its main disadvantages or limitations?

  • Causes significant permanent pressure loss, leading to higher energy costs.
  • Limited turndown ratio (typically 3:1 to 4:1), meaning it's not accurate over a wide flow range.
  • The sharp edge of the orifice can wear over time, affecting accuracy.
  • Requires long straight pipe runs for accurate measurement.

9. Why are straight pipe runs required before and after an orifice plate?

Straight pipe runs are essential to ensure a fully developed and non-swirling flow profile before the fluid reaches the orifice plate. Any disturbances like bends, valves, or reducers can distort the flow profile, leading to significant measurement errors. Standards typically require 10-20 pipe diameters upstream and 5-7 diameters downstream.

10. What are corner taps, D-D/2 taps, and flange taps?

These refer to the locations of the pressure taps:

  • Flange Taps: The most common in the US. Taps are located 1 inch upstream and 1 inch downstream from the plate faces.
  • D and D/2 Taps: Taps are located one pipe diameter (D) upstream and half a pipe diameter (D/2) downstream (near the Vena Contracta).
  • Corner Taps: Taps are located immediately adjacent to the plate faces, in the corners. Common in Europe for smaller pipe sizes.

11. How does fluid viscosity affect the measurement accuracy?

Viscosity affects the flow profile and the discharge coefficient. The flow calculation must account for the Reynolds number, which is a function of viscosity. High viscosity (low Reynolds number) can cause the discharge coefficient to change significantly, leading to inaccuracies. For highly viscous fluids, a quadrant edge orifice plate is often preferred.

12. What is the role of the Reynolds number in orifice flow measurement?

The Reynolds number (Re) is a dimensionless quantity that describes the flow pattern (laminar vs. turbulent). The discharge coefficient (Cd), a key factor in the flow equation, is dependent on the Reynolds number. For accurate measurement, the flow should be turbulent (typically Re > 4000), where the discharge coefficient is relatively constant and predictable.

13. What happens if the orifice plate is installed backward?

An orifice plate has a square, sharp edge on the upstream side and a beveled edge on the downstream side. If installed backward, the beveled edge faces the flow. This creates a much different flow pattern and pressure profile, leading to a lower differential pressure for the same flow rate. The meter will read significantly lower than the actual flow, resulting in large measurement errors.

14. Explain the purpose of a drain or vent hole in an orifice plate.

A small hole is sometimes drilled into the plate to allow unwanted phases to pass through.

  • Vent Hole (Top): In a horizontal pipe carrying liquid, a vent hole at the top allows trapped gas or vapor to pass, preventing it from accumulating.
  • Drain Hole (Bottom): In a horizontal pipe carrying gas, a drain hole at the bottom allows condensed liquid to pass, preventing it from building up.

15. How do you measure the flow of wet gas or steam?

For wet steam or gas, a drain hole at the bottom of the plate in a horizontal line is crucial to drain condensate. Alternatively, the meter can be installed in a vertical pipe with the flow moving downwards, which helps keep the liquid phase moving. It's also important that the pressure taps are oriented correctly (typically at the side) to prevent them from filling with liquid.

16. What is "turndown ratio" and how does it apply to orifice meters?

Turndown ratio is the ratio of the maximum to the minimum flow rate that a meter can measure accurately. Orifice plates have a poor turndown ratio, typically 3:1 or 4:1. This is because the differential pressure is proportional to the square of the flow rate. At low flow rates, the pressure drop becomes very small and difficult to measure accurately, limiting the meter's effective range.

17. What are some common causes of inaccuracy in orifice meter readings?

  • Incorrect installation (e.g., backward plate, wrong gasket).
  • Wear and tear on the sharp edge of the orifice.
  • Insufficient straight pipe runs causing flow disturbances.
  • Incorrect dimensions entered into the flow computer.
  • Pulsating flow.
  • Blocked or leaking impulse lines to the DP transmitter.

18. How would you troubleshoot a reading that is unexpectedly low?

First, check for process changes. If the process is normal, I would:

  • Check the DP transmitter for errors or calibration drift.
  • Inspect the impulse lines for leaks, blockages, or trapped fluids.
  • Verify that the bypass and equalization valves on the transmitter manifold are fully closed.
  • If possible, inspect the orifice plate to see if it's installed backward, damaged, or has the wrong bore size.

19. Compare an orifice meter to a Venturi meter.

Both work on Bernoulli's principle. However, a Venturi meter has a gradual, tapered inlet and outlet. This design results in a much lower permanent pressure loss (about 10-20% of the DP) compared to an orifice plate (40-80% of DP). Venturi meters are more expensive, larger, but more energy-efficient and less prone to wear. Orifice plates are cheaper and easier to install but waste more energy.

20. What safety precautions should be taken when working with orifice meter installations?

Safety is paramount. Key precautions include:

  • Following proper Lock-Out/Tag-Out (LOTO) procedures before starting work.
  • Depressurizing and draining the section of pipe before removing flanges.
  • Using appropriate Personal Protective Equipment (PPE) for the specific fluid and conditions.
  • Ensuring correct gaskets are used and bolts are torqued to specification during reassembly to prevent leaks.